Calculator · Thermal Engineering

Overall Heat-Transfer Coefficient

Hot convection, plane-wall conduction and cold convection with one explicit common reference area.

Inputs

Results

Hot convection0.02 K/W
Wall conduction0.125 K/W
Cold convection0.05 K/W
Total resistance0.195 K/W
Overall U · common area A2.5641 W/(m²·K)
Conductance UA5.1282 W/K
Reference area2 m²

Assumptions

  • · Plane wall; one common reference area A on both sides. No cylindrical-area equivalence or inferred fouling.

Explore in the Lab

Open in Heat Exchanger Lab

Transfers UA only; inlet temperatures and capacity rates are editable example streams, not inferred from the wall.

Technical reference

Rtotal = 1/(hhA) + L/(kA) + 1/(hcA)

UA = 1/Rtotal

U = UA/A

Single-phase constant-capacity streams; parallel or counterflow only.

LMTD uses known outlets; no underdetermined state is guessed.