Calculator · Fluid Mechanics

Minor Loss Calculator

Fittings, bends, valves, entries and exits dissipate head locally. Each is described by a loss coefficient K ≥ 0 acting on the velocity head of the section the coefficient refers to.

Inputs

Group several fittings by adding their coefficients, as long as they all refer to the same section.

Only needed for the pressure-drop form.

Results

Minor head loss h_m = K V²/(2g)

1.1472 m

A nonnegative magnitude, like every loss in this domain.

Loss coefficient K2.5
Mean speed V3 m/s
Fluid density ρ1000 kg/m³
Minor head loss h_m1.1472 m
Pressure drop Δp_m = ρ g h_m11.25 kPa

Explore in the Lab

Add this fitting to a pipe run in the Pipe Flow Lab

The Lab adds the minor loss to the major loss of the same segment.

Technical reference

h_m = K V² / (2g)

Δp_m = ρ g h_m

V = Q / A

h_m
local (minor) head loss[m]
K
loss coefficient of the fitting, K ≥ 0[-]
V
mean speed of the reference section[m/s]
ρ
density of the fluid[kg/m³]

A negative K is not a valid loss model: a fitting cannot add energy to the flow.

A coefficient always refers to a stated section. Adding coefficients that refer to different diameters without converting them is a modelling error.

Reference case: K = 2.5 at V = 3 m/s gives h_m ≈ 1.1472 m.