Calculator · Thermal Engineering

Refrigerator & Heat-Pump COP

A reversible refrigerator and a reversible heat pump between the same two reservoirs differ only in which heat stream is the product. Pick the device, enter both absolute temperatures, and read the COP and the work a stated heat duty requires.

Inputs

Ideal cycle limits: reversible Carnot models between two reservoirs, and ideal air-standard Otto, Diesel and Brayton cycles with constant specific heats. Real machines fall below these values.

Results

COP

5.4

Reversible (Carnot) limit. Heat-pump COP = refrigerator COP + 1 for the same reservoirs.

Heat lift Q_C100 kJ
Work input W18.519 kJ
Heat rejected Q_H118.52 kJ
Refrigerator COP5.4
Heat-pump COP (same reservoirs)6.4

Assumptions

  • · reversible cycle
  • · two reservoirs

Explore in the Lab

Open this cycle in the Thermodynamic Cycles Lab

The full cycle state travels; the Lab adds the state diagram and the comparison view.

Technical reference

COP_R = T_C / (T_H − T_C)

COP_HP = T_H / (T_H − T_C)

COP_HP = COP_R + 1

T_H
hot reservoir temperature (absolute)[K]
T_C
cold reservoir temperature (absolute)[K]
r
compression ratio[—]
r_c
cutoff ratio[—]
r_p
pressure ratio[—]
γ
heat-capacity ratio cp/cv[—]

Temperatures are absolute (kelvin); equal or inverted reservoirs are refused.

These are reversible ideal limits — every real device between the same reservoirs has a lower COP.